The DataCentre

Fortis DataCentre offers 4 x 1,000 sqm DataHalls within 2 joined DataCentres.

Fortis offers the following flexible, high quality accommodation to its occupiers.

 

 

  • Building
    • Two loading bays and two 200kg lifts for equipment
    • Control room/bridge for each hall
    • Braced Sttel framed building
    • Warm roof construction, three layer ashphalt weatherproofing system on concrete slab
    • Dedicated tenant plant areas on roof
    • Landlord fire alarm to BS5839 Category L2/P1
    • 48 Car Parking Spaces
  • Data Hall Layout
    • Each hall 1000m2 net, PDUs within hall, CCU's in plant corridor
    • 800mm clear floor void (1200mm on upper floor)
    • 4000mm internal height, data hall floor to soffit
    • No internal shear walls, bracing or load bearing walls, allowing maximum future felxibility
    • 2 hour fire resistance to structural frame
    • Sustainable surface water drainage system
    • Data Hall Floor loading:-
      - Imposed loading 12kN/m2 over complete building footprint
      - Ceiling and services 2.4 kN/m2
      - Raised access floor 0.6kN/m2
  • DataHall Mechanical & Electrical Services
    • Modular fit out with plant dedicated to each hall
    • 4kW/m2 with options to extend to 7 kW/m2 +
    • Tier IV electrical and Tier III mechanical
    • Tenant owned 11kV switchgear and transformers
    • Landlord generator for building services
    • Tenant owned generators and bulk fuel storage external to building
    • 6 hour day tank plus bulk fuel storage for 72 hours operation
    • Modular static UPS arrangement up to 2400kVA to allow for load growth
    • 10 minute battery autonomy on each UPS. Options for 15 minute autonomy
    • Dedicated battery room for efficient temperature management
    • 10 No x 400A PDUs per stream/per hall (20 No. per hall)
    • All PDUs dual fed from separate streams
    • Overhead power and underfloor data strategy proposed
    • 3 chillers per hall, operating 2 + 1
    • 24 CCUs per hall, operating 18 + 6, all electricity dual fed
    • Resilient pipework distribution design allowing partial isolation whilst retaining full operation
    • Free cooling incorporated within chilled water plant design
    • Options for chilled water connections to meet high density cooling application
    • Inverter driven pumps
    • Options for hot or cold aisle containment
    • 10% of floor tiles provided as grilles
    • Possibility of fresh air cooling to 2 halls on upper floor
    • Leak detection
    • Automatic Fire Detection to BS5839 and BS6266
    • Gas suppression solution to halls, with tenant bottle storage areas
    • High sensitivity aspirating smoke detection in hall
    • Options for hi-fog/sprinklers to plant areas
    • BMS and SCADA system control and measurement
    • Full access control and security system, including CCTV and biometric readers
    • Options for Low and Zero Carbon technologies